Novoflex N-HAR H05VV5-F 4-N UL/CSA
Harmonized PVC-sheathed control cable UL/CSA
- 2 (3)
- 3 (5)
- 4 (5)
- 5 (5)
- 7 (5)
- 12 (5)
- 18 (5)
- 25 (5)
- 34 (2)
- 0.5 (8)
- 0.75 (9)
- 1 (9)
- 1.5 (7)
- 2.5 (7)
- No (3)
- Yes (37)
E-number | Dimension n x mm² | Outer diameter mm | Weight kg/100m |
N7641020 | 2x0,5 | 5.8 | 4 |
N7641030 | 3G0,5 | 6.1 | 5.1 |
N7641040 | 4G0,5 | 6.9 | 6.2 |
N7641050 | 5G0,5 | 7.5 | 7.5 |
N7641070 | 7G0,5 | 9 | 11.7 |
N7641120 | 12G0,5 | 10.7 | 18.8 |
N7641180 | 18G0,5 | 12.9 | 24.8 |
N7641250 | 25G0,5 | 16 | 34.8 |
N7642020 | 2x0,75 | 6.4 | 4.3 |
N7642030 | 3G0,75 | 6.7 | 6.1 |
N7642040 | 4G0,75 | 7.3 | 7.5 |
N7642050 | 5G0,75 | 8.2 | 10 |
N7642070 | 7G0,75 | 9.9 | 14.1 |
N7642120 | 12G0,75 | 12.1 | 23 |
N7642180 | 18G0,75 | 14.2 | 30.6 |
N7642250 | 25G0,75 | 16.5 | 42.7 |
N7642340 | 34G0,75 | 19.5 | 59 |
N7643020 | 2x1 | 6.7 | 5.7 |
N7643030 | 3G1 | 7.1 | 7.1 |
N7643040 | 4G1 | 7.8 | 8.9 |
N7643050 | 5G1 | 8.7 | 11.6 |
N7643070 | 7G1 | 10.5 | 16.6 |
N7643120 | 12G1 | 12.5 | 25.1 |
N7643180 | 18G1 | 15 | 38.5 |
N7643250 | 25G1 | 17.5 | 53.4 |
N7643340 | 34G1 | 21 | 70 |
N7644030 | 3G1,5 | 8.3 | 9.2 |
N7644040 | 4G1,5 | 9.1 | 12.8 |
N7644050 | 5G1,5 | 10.2 | 15.5 |
N7644070 | 7G1,5 | 12.5 | 22.7 |
N7644120 | 12G1,5 | 14.5 | 33 |
N7644180 | 18G1,5 | 17.7 | 50.6 |
N7644250 | 25G1,5 | 20.4 | 70 |
N7645030 | 3G2,5 | 9.9 | 14.6 |
N7645040 | 4G2,5 | 11 | 19.6 |
N7645050 | 5G2,5 | 12.1 | 23.5 |
N7645070 | 7G2,5 | 14.7 | 34.3 |
N7645120 | 12G2,5 | 17.4 | 53.5 |
N7645180 | 18G2,5 | 21.3 | 80 |
N7645250 | 25G2,5 | 25.6 | 110 |
Standard:
VDE 0295, HD21.13 S1
Approvals:
Complies to Swedish and European standard acc. to SS EN 60204, Style 2587, HAR-approved
Rated Voltage Uo/U:
300/500V
Rated Voltage acc to. UL/CSA:
600V
Conductor class:
Class 5 = fine stranded wires
Conductor material:
Copper
Core insulation:
PVC
Core identification:
Black with white numerals
Protective conductor:
Yellow/Green
Outer sheath:
Special PVC
Sheat colour:
Grey RAL 7001
Bending radius fixed:
4 x cable diameter
Bending radius moved:
15 x cable diameter
Min operating temperature fixed:
-40°C
Max operating temperature fixed:
HAR: +70°C UL/CSA: +90°C
Min operating temperature moved:
-5°C
Max operating temperature moved:
HAR: +70°C UL/CSA: +90°C
Testing voltage:
3000V
Insulation resistance:
≥20 MOhm x km
Flame retardant:
IEC 60332-1, UL1581 VW1, CSA FT1