Novoflex NCY-UV-UL 2-N UL/CSA

Shielded UV-resistant control cable UL/CSA 0,6/1kV
  • 2 (2)
  • 3 (2)
  • 4 (8)
  • 5 (2)
  • 7 (2)
  • 12 (2)
  • 18 (2)
  • 25 (2)
  • 1 (8)
  • 1.5 (8)
  • 2.5 (1)
  • 4 (1)
  • 6 (1)
  • 10 (1)
  • 16 (1)
  • 25 (1)
  • No (2)
  • Yes (20)
E-numberDimension n x mm²Outer diameter mmWeight kg/100m
N79420202x1,06.36.5
N79420303G1,06.77.7
N79420404G1,07.29.7
N79420505G1,07.811.3
N79420707G1,08.414.1
N794212012G1,010.922.4
N794218018G1,012.944
N794225025G1,017.651.4
N79430202x1,56.97.9
N79430303G1,57.310
N79430404G1,57.912.1
N79430505G1,58.614.7
N79430707G1,59.318.5
N794312012G1,512.330.2
N794318018G1,514.845.4
N794325025G1,51759.5
N79440404G2,58.717.9
N79450404G4,010.526.2
N79460404G6,012.438.4
N79470404G1015.961.6
N79480404G1618.789.1
N79490404G2523.8138
Standard:
IEC 60828, DIN-EN 50290-2-22, UL 1581, CSA FT1, UL VW1, CEI 20-22 II, NBN C30-004 CAT F2
Approvals:
UL/CSA: cULus-90°C/ 1000V, VDE
Rated Voltage Uo/U:
300/500V
Rated Voltage acc to. UL/CSA:
1000V
Conductor class:
Class 5 = fine stranded wires
Conductor material:
Copper
Core insulation:
PVC
Core identification:
Black with white numerals
Protective conductor:
Yellow/Green
Overall shield:
Braided tinned copper wire
Shield coverage:
Approx. 85%
Outer sheath:
PVC
Sheat colour:
Black RAL 9005
Bending radius fixed:
4 x cable diameter
Bending radius moved:
20 x cable diameter
Min operating temperature fixed:
-40°C
Max operating temperature fixed:
+90°C
Min operating temperature moved:
-5°C
Max operating temperature moved:
+90°C
Testing voltage:
6000V
Conductor resistance:
See technical appendix
Flame retardant:
IEC 60332-3-24